next up previous
Next: Results and Discussion Up: RECURSIVE PROPORTIONAL-FEEDBACK AND ITS Previous: Experimental System

Control Method

The RPF control strategy[3] was used to stabilize both period-1 and period-2 orbits within chaotic attractors measured by a time series of the anodic current. A Poincaré section was taken at the time when the anodic current goes through a minimum. A one-dimensional return map was constructed from the sequence of current minima where is the current minimum at the beginning of the nth Poincaré cycle. The value of the anodic potential during the nth cycle is . According to the RPF algorithm, control is established by adding an increment to the anodic potential during the nth cycle given by[2,3]

 

where is the unstable fixed point of the target orbit for the return map obtained for a time series taken at . The value of and the constants K and R, are determined from a precontrol experimental procedure carried out using an interactive computer program for data acquisition and display.

The precontrol procedure is described in detail in references[2,3]. Firstly, the fixed point and the slope, , of the one-dimensional return map was determined by a least square fitting of the displayed return map ( versus ) for a sequence of current minima collected in the neighborhood of the desired fixed point with the anodic potential held constant at . Secondly, a sequence of current minima were collected and displayed as a return map while the anodic potential is changed back and forth between two values; for n odd and for n even. The value of was chosen to be about the size of the maximum used later during control. If the system is sufficiently dissipative, as our electrochemical system was, the resulting return map consists of two curves called the up and back maps formed from alternate (, ) pairs with n odd and even respectively. The shift in the fixed point per unit is measured by least squares fitting for the up and back maps giving and respectively. The values of K and R were then calculated using the RPF relations[3]

 

Typically these control constants, K and R, could be determined within 10--20 minutes (corresponding to approximately 200 cycles of the experimental return map) from the start of data acquisition.

With these control constants available, the control algorithm was initiated. The anodic potential was changed according to the RPF algorithm of Eq. 1 whenever a minimum of the anodic current, , came within about 0.2 mA of the measured fixed point .



next up previous
Next: Results and Discussion Up: RECURSIVE PROPORTIONAL-FEEDBACK AND ITS Previous: Experimental System



Roger Rollins
Wed Nov 15 12:11:04 EST 1995